Home / Journal / Cinematography
Power Distribution on a Film Set: Cables, Grounding, Load and Generators
How set power is fed and protected: feeder cable, distribution boxes, grounding, wire gauge, load calculation and generator sizing, with a worked HMI example.

Good lighting depends on safe, sufficient power. This article follows electricity from the generator to the lamp: how it is distributed, why every portable fixture needs a ground, how to choose a cable, and how to calculate the load and size a generator.
Key points
- Switch ratings should exceed the continuous load by at least 20–25% to survive inrush currents.
- All portable AC lighting gear needs a three-conductor grounded system: hot, neutral and ground. Two-wire ungrounded cable is a shock hazard.
- Lower AWG numbers mean thicker wire with higher current capacity. Coiled cable traps heat and must be unrolled under heavy load.
- Current = watts / volts. For a lamp on a magnetic ballast, current = watts / (volts × power factor), with a power factor of about 0.6–0.7.
- Keep a 15–20% safety margin between the connected load and generator capacity.
The distribution chain
Power travels from the generator through heavy single-conductor feeder cables (4/0, 2/0 or #2 with Cam-Lok connectors) to distribution boxes, then through extension cords to the fixtures. A three-phase four-wire feeder set has five conductors: phases A, B and C (black, red and blue), neutral (white) and ground (green). In the distribution box (“lunchbox”) circuit breakers split the heavy feeder into 20 A branch circuits ending in stage-pin, twist-lock or household outlets. Short extensions, or “stingers”, are made of 12/3 or 10/3 rubber cable.

Power distribution chain on a film set
Single-pole switches serve loads up to 2 kW; heavier 220–240 V circuits use double-pole switches that open both hot legs. Conductor colours are Black or Brown for hot, White or Blue for neutral and Green or Green-Yellow for ground, depending on the national standard.

Five-wire three-phase feeder set
Why grounding matters
If an ungrounded wire frays inside a metal fixture, the whole housing can become live, and a person touching it becomes the path of least resistance to earth. A ground conductor does the opposite job: it carries the fault current safely to earth and trips the breaker. Generators and distribution panels must be bonded to earth with ground rods or structural steel.
Cable and wire gauge
Wire thickness is given in American Wire Gauge or in square millimetres. The lower the AWG number, the thicker the wire and the more current it can carry, from 4/0 feeder cable down to 18 AWG for control wires. Thick copper has low resistance, so it heats less and loses less voltage. Feeder cable needs a heat-resistant neoprene or EPDM jacket with a fibreglass braid; the wiring inside a fixture uses silicone-insulated, fibreglass-sleeved conductors.
Calculating the load
Before switching on, add up the load: amps = watts / volts. A resistive tungsten lamp is simple. An HMI on a magnetic ballast draws more than its rating suggests because of the power factor. For example, four 1,200 W HMI heads on 120 V with a power factor of 0.65 draw 4,800 / (120 × 0.65) ≈ 61.5 A in total, not the 40 A that the watts alone would suggest.
Generators
A production generator is a diesel or gas engine driving an alternator. An electronic governor holds the frequency at 50 or 60 Hz. The set is sized by its maximum continuous output in kW or kVA, with 15–20% in reserve. HMI units run on AC; old carbon arcs needed pure DC. As fixtures are added to a circuit the total current rises in proportion, and the breaker rating limits the capacity of each branch.
Quick answers
Why does coiled cable overheat? Current produces heat in the conductor (I²R), and a coil traps it instead of letting it dissipate.
What does a lower AWG number mean? A thicker conductor with a higher safe current.
Why is an HMI load higher than its wattage suggests? The magnetic ballast has a power factor below 1, so the supply must deliver more current for the same power.
Read next
- Alternating Current, Transformers and Three-Phase Power for Film Crews
- HMI, Fluorescent and Flash: Discharge Light Sources for Film
- Ballasts, Flicker and Camera Sync for Film Lights
Related on this site
This article is part of the free handbook Technical Foundation. Filmmaking: The Cinematographer’s Handbook by Semen Klenov, an independent researcher of light and visual perception. Cite the handbook as: Klenov, S. (2026). Technical Foundation. Filmmaking: The Cinematographer’s Handbook. Zenodo. https://doi.org/10.5281/zenodo.24326083.